Gree Corporation 2014 V2.0 Page 1
Multi-Room Ductless heat-pump systems
Submittal Data: MULTI24HP230V1AO
24,000 BTU/H Wall Mounted Heat- Pump System
Job Name Location Date
Purchaser Engineer
Submitted To For
Unit Designation Schedule No.
GENERAL FEATURES
-Up to 3 Indoor Units Comfort (3-Port)
-G10 DC Inverter Technology
-Quiet Operation - Both Indoor & Outdoor
-Wireless Remote Controller
-Optional Wired Remote Controller
-Gold Fin Coil Coating
-Intelligent Defrost
-Auto Restart on Power Outages
-Limited 7 yr Compressor & 5 yr Parts Warranty
Cooling Compressor Type DC Inverter Driven Rotary
Rated Capacity 26,000 BTU/H RLA 10.0 A
Capacity Range 7,500-33,000 BTU/H
Power Input (Max) 3,050 W Fan Motor Output Power 60 W
SEER 16 FLA 0.6 A
EER 8.2 Air Flow (Max) 1,530 CFM
Heating at 47° F
Rated Capacity 29,000 BTU/H Sound Pressure
Capacity Range 7,500-35,000 BTU/H Cooling 56 db(A)
Input Power (Max) 2,800 W Heating 56 db(A)
HSPF 8.2
COP 3.0 Dimensions & Weights
Heating at 17° F Unit Dimensions (LxHxD) 37.2 x 27.6 x 15.6 -in
Rated Capacity 17,000 BTU/H Weight (Net/Shipping) 134/146 LBS
Capacity (Max) 23,715 BTU/H
Min. Number of Indoor Units 2
Operating Range
Max. Number of Indoor Units 3
Cooling (Max)
118℉ (48 C)
(Min)
23℉ (-5 C) Connection Method Flared
Heating (Max)
80℉ (27 C) Refrigerant Type R410A
(Min)
5℉ (-15 C) Factory Charge for Total Line Length 98-ft
Additional Charge Per Line Length 0.2-oz/ft
Power Supply Total Refrigerant Pipe Length 230-ft
Normal Operational Voltage
208/230 V, 1 Phase, 60 Hz Max Refrigerant Piping Length to any Indoor Unit 66-ft
Voltage Range
187 - 253 V Min Refrigerant Piping Length to any Indoor Unit 10-ft
Main Power Wire Size
10-2 AWG Max Elevation between Indoor Units 33-ft
Interconnecting Cable Wire Size
14-4 AWG Max Lift from Outdoor to Indoor Unit 66-ft
MCA
20.0 A Max Drop from Outdoor to Indoor Unit 66-ft
MOCP/Breaker Size
30 A
AHRI Certified Ref No: 7084908